Mounting and installation – VEGA VEGAPULS 51K…54K Profibus PA User Manual

Page 23

Advertising
background image

VEGAPULS 51P … 54P

23

24890-EN-041227

Mounting and installation

0 %

~45˚

100,8

0,0…0,4

1,5…2

3,6

0,0…0,4

150…500

5…10

3,6

96

2

100 %

VEGAPULS 54

Flange DN 100

Connecting
sleeve

Welding neck
flanges

Welding of the smooth
welding neck flanges

Welding of the connect-
ing sleeves

Meas. pipe fastening

Vessel
bottom

Deflector

Rz

≤ 30

Deburr the
holes

Welding of the welding
neck flange

0 %

0 %

Quadrant pipe on the bypass tube end

Quadrant pipe on the standpipe end

If the vessel contains agitated products,
fasten the measuring pipe to the vessel bot-
tom. Provide additional fastenings for longer
measuring pipes.

In products with lower dielectric values (< 4),
a part of the radar signal penetrates the
medium. If the vessel is nearly empty, echoes
are generated by both the product and the
vessel bottom. The echo from the vessel
bottom can in some cases be stronger than
the echo from the product surface. If a de-
flector is installed below the open end of the
measuring tube, the radar signals are scat-
tered and prevented from reaching the ves-
sel bottom. This ensures that, in nearly empty
vessels or with products of low dielectric
value, the product delivers a more distinct
echo than the vessel bottom.

Due to the deflector, the useful signal and
meas. value in the nearly empty vessel are
distinct and clear - the 0 % level can thus be
reliably measured.

Instead of a deflector, the standpipe or surge
pipe can be equipped with a quadrant pipe
at the end. This quadrant pipe reflects the
radar signals that penetrate the medium
diffusely to the side and diminishes strong
echoes from the tube end or the vessel bot-
tom.