2 application features, 3 profibus output signal – VEGA VEGAPULS 51K…54K Profibus PA User Manual

Page 6

Advertising
background image

6

VEGAPULS 51P … 54P

24890-EN-041227

Product description

1.2 Application features

Applications

• level measurement of any liquid, limited use

in solids

• measurement also in vacuum
• all slightly conductive materials and all

substances with a dielectric constant > 2.0
can be measured

• measuring range 0 … 20 m.

Two-wire technology

• power supply and output signal on one

two-wire cable

• output signal and signal processing com-

pletely digital, therefore maximum accu-
racy

• Profibus profile 3 sensor

Rugged and abrasionproof

• non-contact
• high-resistance materials

Exact and reliable

• accuracy 1 mm.
• unaffected by noise, vapours, dusts, gas

compositions and inert gas stratification

• unaffected by varying density and tem-

perature of the medium

• measurement in pressures up to 40 bar

and product temperatures up to 200°C.

Communicative

• can be networked in any way, with up to 32

sensors on one two-wire cable (digital
output signal) on the segment coupler

• integrated measured value display
• optional display module separate from

sensor

• adjustment with detachable adjustment

module, pluggable in the sensor or in the
external display

• adjustment from the PLC level, on the sen-

sor or on the Master-Class II adjustment
PC.

Approvals

• CENELEC. ATEX. PTB. FM. CSA. ABS.

LRS. GL. LR. FCC.

1.3 Profibus output signal

PRO

PRO

PRO

PRO

PROcess FI

FI

FI

FI

FIeld BUS

BUS

BUS

BUS

BUS (PROFIBUS) is the re-

sult of a joint project of thirteen companies
and five universities. The companies Bosch,
Klöckner-Möller and Siemens played a deci-
sive role. The specifications of the bus are
described in the protocol layers 1, 2 and 7 of
the ISO/OSI reference model and are avail-
able from the PNO (Profibus user organisa-
tion). Since layers 3 to 5 have not yet been
developed as a standard, Profibus still has a
lot of far-reaching potential.

Today approx. 600 companies make use of
Profibus technology and belong to the PNO.
Profibus FMS

FMS

FMS

FMS

FMS stands for Fieldbus Messaging

Specification, Profibus DP

DP

DP

DP

DP for Decentralised

Periphery and Profibus P

P

P

P

PA

A

A

A

A for Process Auto-

mation.

As a process automation bus, Profibus PA
also enables power supply over the bus. Up
to 32 sensors can be operated on a shielded
two-wire cable that carries both power sup-
ply and measuring signal. In Ex areas, up to
ten sensors can be connected from the PA
level to one two-wire cable (EEx ia).

Bus structure

The Profibus DP and PA network consists of
up to 126 master and slave participants.
Data are always exchanged from point to
point, with the data traffic being exclusively
controlled and checked by master devices.
Communication is carried out acc. to the
Token-Passing procedure. This means that
the master holding the Token can contact the
slaves, give instructions, enquire data and
cause the slaves to receive and transmit
data. After the work is done or after a prede-
termined time interval, the Token is passed
on by the master to the next master.

Advertising