Standpipe measurement of inhomoge- neous products, Adhesive products – VEGA VEGAPULS 51K…54K Profibus PA User Manual

Page 20

Advertising
background image

20

VEGAPULS 51P … 54P

24890-EN-041227

ш 5...10

ш 5...10

Openings in a surge pipe for mixing of inhomogene-
ous products

slightly inhomogeneous
liquids

inhomogeneous liquids

homogeneous
liquids

Pipe antenna with DN 50. DN 80. DN 100 and DN 150

DN 150

DN 50

ш 50

ш 150

Standpipe measurement of inhomoge-
neous products

If you want to measure inhomogeneous or
stratified products in a surge pipe, it must
have holes, elongated holes or slots. These
openings ensure that the liquid is mixed and
corresponds to the liquid in the vessel.

In extremely adhesive products, measure-
ment in a standpipe is not possible at all.

Adhesive products

In adhesive products, use a surge pipe with
a larger inner diameter. In non-adhesive
products, a 50 mm measuring tube is a good
and cost-effective solution. In slightly adhe-
sive products, use a surge pipe with a nomi-
nal width of 100 mm or 150 mm. so that
buildup cannot cause measurement errors.

Mounting and installation