3 adjustment without medium – VEGA VEGAMET 614 User Manual

Page 21

Advertising
background image

VEGAMET 614

21

Settings in the "Reduced menu“

Adjustment example

You know the data of the sensor, i.e. you
know that at 0 % filling, the sensor delivers a
current of 4.2 mA and at 100 % filling a cur-
rent of 15.5 mA. Enter these values in the
menu items.

6.3 Adjustment without medium

For this adjustment procedure, you have to
enter two sensor current values (4 … 20 mA)
corresponding to the levels 0 % and 100 %.

TAG-
No. 1
%
xx,x

Param.
TAG-
No. 1

Ad-
just-
ment

with
medium

w.o
medium

0%
at

mA

4,000

100%
at
mA

20,000

Meas.
value
indication

Enter in these two menu items the values of
the senor. Use the [+] and [–] keys to set the
values and [OK] to save the values.

0%
at
mA

4,200

100%
at
mA

15,500

4.2 mA at 0 %

15.5 mA at 100 %

Advertising