13

5 Electrical connection

VEGASCAN 693 • 15-channel HART signal conditioning instrument

29252-EN-130701

2. Connect sensor cable to terminal 1/2 (active input) or 3/4 (passive

input), provide a screening

3. When using several sockets, loop the power supply by means of

bridges

4. Connect power supply (switched off) to terminal 17 and 18
5. If necessary, connect relays or other outputs
6. Insert VEGASCAN 693 into the plug-in socket and screw it down

tightly

Note:

If the addressing of the sensors is not yet carried out, only one sensor

must be connected. Then the addressing (see chapter "Setup") is car-

ried out. Afterwards, the first sensor must be disconnected again and

the next sensor must be connected as well as the addressing must be

carried out. Carry out this procedure as long as all sensors have an

own, unambiguous address. Then all sensors can be connected and

setup can be carried out.
Before setting up Ex versions, make sure the Ex separating chamber

is plugged on the left housing side (above the sensor terminals). The

pins for type and Ex coding must also be inserted correctly.
Information:

On the active input (terminal 1/2), VEGASCAN 693 provides

power for the connected sensors. Power supply and measurement

data are transmitted over the same two-wire cable. This mode is

provided for connection of measuring transducers without sepa-

rate operating voltage (sensors in two-wire version).

On the passive input (terminals 3/4), the sensors are not supplied

with energy - only the measured value is transmitted. This input is

for instruments with their own separate operating voltage (sensors

in four-wire version or separators such as VEGATRENN 149). On

a VEGASCAN 693 in Ex version, the passive input is not available

due to approval/technical reasons.

Note:

VEGASCAN 693 is designed for connection of up to 15 HART sen-

sors (5 with Ex). Because they are accessed via different addresses

in the HART multidrop mode, all sensors must be connected to the

same sensor input. These are either terminals 1/2 (active input) or

terminals 3/4 (passive input). Mixed operation of active and pas-

sive input is not possible. Since this is a digital bus system, only one

two-wire cable should lead to the sensors. A distributor can then be

connected directly forward of the sensors. As an alternative, the con-

nection cable can be looped through the second cable entry on the

sensor housing. The address assignment of the sensors should be

carried out before connection, see chapter "Set up".