11 Supplement

VEGASCAN 693 • 15-channel HART signal conditioning instrument

29252-EN-130701

11 Supplement

11.1 Technical data

General data
Series

Module unit with plug-in socket for mounting on carrier

rail (35 x 7.5 according to DIN EN 50022/60715)

Weight

500 g (1.10 lbs)

Housing materials

Noryl SE100, Lexan 920A

Socket materials

Noryl SE100, Noryl SE1 GFN3

Connection terminals

Ʋ Type of terminal

Screw terminal

Ʋ Max. wire cross-section

1.5 mm² (AWG 16)

Voltage supply
Operating voltage

20 … 253 V AC, 50/60 Hz, 20 … 253 V DC

Max. power consumption

12 VA; 7.5 W

Sensor input
Number of sensors

15 x VEGA HART sensors (5 x with Ex version)

Type of input (selectable)

1)

Ʋ Active input

Sensor power supply by VEGASCAN

Ʋ Passive input

Sensor has an own power supply

Measured value transmission

Ʋ HART multidrop protocol

digital for VEGA HART sensors

Terminal voltage

Ʋ Non-Ex version

approx. 22 V with 15 sensors (60 mA)

Ʋ Ex version

approx. 15 V with 5 sensors (20 mA)

Current limitation

approx. 85 mA (26 mA with Ex)

Adjustment range HART sensor

Ʋ Adjustment range

± 10 % of sensor measuring range

Ʋ min. adjustment delta

0.1 % of sensor measuring range

Connection cable to the sensor

two-wire screened standard cable

Fail safe relay
Contact

Floating spdt

Contact material

AgSnO2, hard gold-plated

Switching voltage

min. 10 mV DC, max. 250 V AC/DC

Switching current

min. 10 µA DC, max. 3 A AC, 1 A DC

Breaking capacity

min. 50 mW, max. 750 VA, max. 40 W DC (with U less

than 40 V)

2)

Ethernet interface (optional)
Quantity

1 x, cannot be combined with RS232

Data transmission

10/100 MBit

Advertising