VEGA VEGASCAN 693 User Manual

Page 18

Advertising
background image

18

6 Setup with the integrated display and adjustment unit

VEGASCAN 693 • 15-channel HART signal conditioning instrument

29252-EN-130701

Internal check of the electronics

indication of the instrument type, firmware version as well as the

instrument TAG (instrument name)

The output signals jump briefly to the set fault value

After the assignment of the addresses to the sensors, the current

measured values will be displayed and outputted.

The measured value indication displays three measured values each

in one common window. The digital display value, the measurement

loop name (meas. loop TAG) and the unit are shown. By pushing the

[>] key, you can move to the next three measured values.
Note:

Depending on the configuration and use of all measurement loops,

the cycle time for the measured value transmission can take up to five

seconds.

By pushing [OK] you move from the measured value indication to the

main menu.

The main menu is divided into six areas with the following functions:

Device settings: Includes the device-TAG, settings for network

connection such as date/time setting, …

Measurement loop: Includes settings for input selection, adjust-

ment, damping, linearization, scaling, …

Display: Includes settings to the displayed measured value

Diagnosis Includes information to the device status, error mes-

sages

Service Includes simulation, reset, PIN, selectable language,

sensor address, …

Info: Shows serial number, software version, last change, instru-

ment features, MAC addr., …

Select the menu item "Device settings" with [->] and confirm with

[OK].

You can assign an unambiguous name to VEGASCAN 693 via the

Device-TAG. This function is recommended when several instruments

are implemented and a good documentation of larger systems is

required.

Measured value indica-

tion

Main menu

Device settings - Device-

TAG