6 Setup with the integrated display and adjustment unit

VEGASCAN 693 • 15-channel HART signal conditioning instrument

29252-EN-130701

Reset on measurement loop: The settings of the selected meas-

urement loop will be set to default. The measurement loop is

deactivated and the TAG name reset to default.

With every 4 … 20 mA/HART sensor, the measured value can be

transmitted via analog current signal or digital HART signal. This is

regulated via the HART mode or the address. If a HART sensor is set

to address 0, the sensor is in the standard mode. Here the measured

value is transmitted digitally on the 4 … 20 mA cable.
In mode HART Multidrop, an address from 1 … 15 is assigned to the

sensor. By doing so, the current is fix limited to 4 mA and the meas-

ured value transmission is only made digitally.
Each sensor connected to VEGASCAN 693 must operate in mode

HART multidrop and must be provided with different addresses in

the range between 01 … 15. Via the menu item "Sensor address", it

is possible to change the address of the connected sensor. For this

purpose, enter the previous address of the sensor (factory setting 0)

and in the next window the new address.
Note:

When addresses are being assigned, only one sensor with the same

address must be connected on the bus. If this is not the case, the sen-

sor cannot be accessed and it is not possible to assign an address.

First of all, enter the previous address of the sensor to be modified

(factory setting 0), then you can enter the selected HART address in

the range of 01 - 15 in the menu "New address". Make sure that no

address is assigned twice.

With instrument versions with integrated RS232/Ethernet interface,

a manual data transmission to a WEB-VV server can be trigger, for

example, for test purposes. Requirement is that a WEB-VV event was

configured in advance via PACTware/DTM.

In the menu item "Info" the following information is available:

Sensor type and serial number

Date of manufacture and software version

Date of last change using PC

Instrument features

MAC address (with interface option Ethernet)

Service - Sensor address

Service - Data transmis-

sion

Info