6 Setup with the integrated display and adjustment unit

VEGASCAN 693 • 15-channel HART signal conditioning instrument

29252-EN-130701

Enter the requested parameters via the appropriate keys and

save your settings with [OK].

In the menu item "Display - Indication value", you can set the re-

quested indication value. The following options are available:

Percent: adjusted measured value without taking a probably

stored linearization into account

Lin. percent: adjusted measured value by taking a probably

stored linearization into account

Scaled: adjusted measured value by taking a probably stored

linarization into account as well as the values entered under "Scal-

ing"

Sensor value: input value delivered by the sensor. Presentation in

the selected adjustment unit

Enter the requested parameters via the appropriate keys and

save your settings with [OK].

When the instrument displays a failure message, further information is

available under the menu item "Diagnosis - Device status".

The simulation of a measured value is used to check the outputs and

connected components. The simulation can be applied to the percent-

age value, the lin. percentage value and the sensor value.
Note:

Please note that connected system parts (valves, pumps, motors,

control systems) are influenced by the simulation, thus unintentional

plant operating conditions can occur. The simulation is terminated

automatically after approxminately 10 minutes.

Carry out your settings via the appropriate keys and save with

[OK].

There are two reset modes:

Reset to default: with only a few exceptions, all settings will be

reset to default. Exceptions are: Host name, IP-addr., subnet

mask, time, language.

Display

Diagnostics

Service - Simulation

Service - Reset