4 Mounting
VEGASON 63 • Profibus PA
28786-EN-130417
By using a standpipe (surge or bypass tube), the influence of vessel
installations, foam generation and turbulence is excluded.
Standpipes must extend all the way down to the requested min. level,
as measurement is only possible within the tube.
max.
min.
1
Fig. 14: Standpipe in the tank
1 Vent hole ø 5 … 10 mm
VEGASON 63 can be used from tube diameters of 100 mm.
Avoid large gaps and thick welding joints when connecting the tubes.
Generally carry out a false echo storage.
Measurement in a standpipe is not recommended for adhesive
products.
Standpipe measurement