47

10 Supplement

VEGASON 63 • Profibus PA

28786-EN-130417

Status

code

Description according to

Profibus standard

Possible cause

0 x 51

uncertain - sensor; conversion

not accurate - low limited

Sensor value < lower limit

0 x 52

uncertain - sensor; conversion

not accurate - high limited

Sensor value > upper limit

0 x 80

good (non-cascade) - OK

OK

0 x 84

good (non-cascade) - active

block alarm

Static revision (FB, TB) changed (10 sec. active, after the parame-

ter of the static category has been written)

0 x 89

good (non-cascade) - active ad-

visory alarm - low limited

Lo-Alarm

0 x 8a

good (non-cascade) - active ad-

visory alarm - high limited

Hi-Alarm

0 x 8d

good (non-cascade) - active crit-

ical alarm - low limited

Lo-Lo-Alarm

0 x 8e

good (non-cascade) - active crit-

ical alarm - high limited

Hi-Hi-Alarm