VEGA VEGASON 64 Foundation Fieldbus User Manual
Page 25
3
Remove approx. 10 cm (4 in) of the cable mantle (current output),
strip approx. 1 cm (0.4 in) insulation from the ends of the individual
wires
4
Insert the cable through the cable gland into the sensor
5
Lift the opening levers of the terminals with a screwdriver
6
Insert the wire ends into the open terminals according to the wiring
plan
7
Press down the opening levers of the terminals, you will hear the
terminal spring closing
8
Check the hold of the wires in the terminals by lightly pulling on
them
9
Connect the screen to the internal ground terminal, connect the
outer ground terminal with potential equalisation
10 Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
11 Connect the lead cable for power supply in the same way
according to the wiring plan, in addition connect the ground
conductor to the inner ground terminal.
12 Screw the housing cover on
The electrical connection is finished.
Fig. 19: Connection steps 5 and 6
VEGASON
64 • Foundation Fieldbus
25
5 Connecting to power supply
28793
-
EN
-081127