10 supplement, 1 technical data – VEGA VEGASON 64 Foundation Fieldbus User Manual
Page 48
10 Supplement
10.1 Technical data
General data
Materials, wetted parts
-
Flange
PP or Aluminium
-
Swivelling holder, flange
galvanized steel
-
Transducer
PA (1.4301 with StEx)
-
Transducer diaphragm
316Ti
Materials, non-wetted parts
-
Housing
Aluminium die-casting powder coated
-
Seal between housing and housing
cover
Silicone
-
Inspection window in housing cover
Polycarbonate (UL-746-C listed)
-
Ground terminal
316Ti
-
transducer cable with separate version C
and D
PUR (1.1082)
Weight
5)
-
Compact with flange (version A)
5.6 … 10.7 kg (12.3 … 23.6 lbs)
-
Compact with swivelling holder
(version B)
6.9 … 9.7 kg (15.2 … 21.4 lbs)
-
Separate with swivelling holder
(version C)
7.5 … 10.5 kg (16.5 … 23.1 lbs)
-
Separate with threaded fitting (version D)
4.7 … 6.9 kg (10.4 … 15.2 lbs)
Output variable
Output
-
Signal
digital output signal, Foundation Fieldbus protocol
-
Physical layer
according to IEC 61158-2
Channel Numbers
-
Channel 1
Primary value
-
Channel 2
Secondary value 1
-
Channel 3
Secondary value 2
Transmission rate
31.25 Kbit/s
Current value
10 mA, ±0.5 mA
Damping (63 % of the input variable)
0 … 999 s, adjustable
5)
Depending on size and process fitting material.
48
VEGASON
64 • Foundation Fieldbus
10 Supplement
28793
-EN
-081127