VEGA VEGASON 64 Profibus PA User Manual
Page 25
1
2
3
Fig. 18: Plug connector between transducer and socket of electronics housing
1
Socket electronics housing
2
Plug connector
3
Connection piece, transducer tube
Only then, the sensor may be connected to voltage supply.
Proceed as follows:
1
Unscrew the housing cover
2
Loosen compression nut of the cable entry
3
Remove approx. 10 cm (4 in) of the cable mantle (current output),
strip approx. 1 cm (0.4 in) insulation from the ends of the individual
wires
4
Insert the cable through the cable gland into the sensor
5
Lift the opening levers of the terminals with a screwdriver
6
Insert the wire ends into the open terminals according to the wiring
plan
7
Press down the opening levers of the terminals, you will hear the
terminal spring closing
8
Check the hold of the wires in the terminals by lightly pulling on
them
9
Connect the screen to the internal ground terminal, connect the
outer ground terminal with potential equalisation
10 Tighten the compression nut of the cable entry. The seal ring must
completely encircle the cable
11 Connect the lead cable for power supply in the same way
according to the wiring plan, in addition connect the ground
conductor to the inner ground terminal.
12 Screw the housing cover on
VEGASON
64 • Profibus PA
25
5 Connecting to power supply
28787
-
EN
-081127