Fig. 8: Flange mounting of the radar sensor

4

.3 Mounting instructions

Mount VEGAPULS 67 at least 200 mm (7.874 in) away from the vessel
wall.

If you cannot keep this distance you should carry out a false echo
storage before setup. This applies mainly if buildup on the vessel wall
is expected. In this case, we recommend repeating a false echo
storage later with existing buildup.

To detect nearly the complete vessel volume the sensor should be
directed in such a way that the measuring beam reaches the lowest
level in the vessel, i.e. the outlet.

Mounting position

Orientation

VEGAPULS

67 • Foundation Fieldbus

17

4 Mounting

32941

-

EN

-100514