3 mounting instructions – VEGA VEGAPULS 67 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual
Page 17
Advertising
Fig. 8: Flange mounting of the radar sensor
4
.3 Mounting instructions
Mount VEGAPULS 67 at least 200 mm (7.874 in) away from the vessel
wall.
If you cannot keep this distance you should carry out a false echo
storage before setup. This applies mainly if buildup on the vessel wall
is expected. In this case, we recommend repeating a false echo
storage later with existing buildup.
To detect nearly the complete vessel volume the sensor should be
directed in such a way that the measuring beam reaches the lowest
level in the vessel, i.e. the outlet.
Mounting position
Orientation
VEGAPULS
67 • Foundation Fieldbus
17
4 Mounting
32941
-
EN