3 exchanging the electronics module, 4 software update – VEGA VEGAPULS 67 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual

Page 50

Advertising
background image

?

E

113

l

Communication conflict

à Exchange the instrument or send it in for repair

Depending on the failure reason and measures taken, the steps
described in chapter "Set up" must be carried out again, if necessary.

8

.3 Exchanging the electronics module

If the electronics module is defective, it can be replaced by the user.

In Ex applications only one instrument and one electronics module with
respective Ex approval may be used.

If there is no electronics module available on site, one can be ordered
from the VEGA agency serving you.

The new electronics module must be loaded with the settings of the
sensor. These are the options:

l

At the factory by VEGA

l

Or on site by the user

In both cases, the sensor serial number is necessary. The serial
numbers are stated on the type label of the instrument, inside the
housing or on the delivery note.

Information:
When loading on site, first of all the order data must be downloaded
from the Internet (see operating instructions manual "Oscillator").

The electronics modules are adapted to the respective sensor and
distinguish also in the signal output or power supply.

Electronics module PS-E.60SF suitable for VEGAPULS 67 and 68 -
Foundation Fieldbus:

l

PS-E.60SFX (X = without approvals)

l

PS-E.60SFD (D = approvals KX, KF according to product list)

l

PS-E.60SFG (CG = approvals CX, DX, CK, DI, EX, GI, UX, UF
according to product list)

8

.4 Software update

The software version of VEGAPULS 67 can be determined as follows:

l

on the type label of the electronics

l

via the indicating and adjustment module

l

via PACTware

Reaction after fault rec-
tification

Sensor serial number

Assignment

Foundation Fieldbus

50

VEGAPULS

67 • Foundation Fieldbus

8 Maintenance and fault rectification

32941

-EN

-100514