VEGA VEGAPULS 67 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus User Manual

Page 49

Advertising
background image

Error

Cause

Removal

When an additio-
nal instrument is
connected, the H1
segment fails.

Max. supply cur-
rent of the seg-
ment coupler
exceeded

Measure the current consumption,
reduce size of segment

Measured value
on the indicating
and adjustment
module does not
correspond to the
value in the PLC

The menu item
"

Display - Dis-

play value

"

is

not set to "

AI-

Out

"

Check values and correct, if neces-
sary

Instrument does
not appear during
connection setup

Profibus DP cab-
le pole-reversed

Check cable and correct, if necessary

Incorrect termina-
tion

Check termination at the beginning
and end points of the bus and termin-
ate, if necessary, according to the
specification

Instrument not
connected to the
segment

Check and correct, if necessary

In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.

?

E

013

l

no measured value available

à Sensor in boot phase
à Sensor does not find an echo, e.g. due to faulty installation or

wrong parameter adjustment

?

E

017

l

Adjustment span too small

à Carry out a fresh adjustment and increase the distance

between min. and max. adjustment

?

E

036

l

no operable sensor software

à Carry out a software update or send instrument for repair

?

E

041, E042, E043

l

Hardware error, electronics defective

à Exchange the instrument or send it in for repair

Error messages via the
indicating and adjust-
ment module

VEGAPULS

67 • Foundation Fieldbus

49

8 Maintenance and fault rectification

32941

-

EN

-100514

Advertising