VEGA VEGAFLEX 66 (-110…+400°C) Foundation Fieldbus User Manual

Page 40

Advertising
background image

?

Measured value on the indicating and adjustment module
does not correspond to the value in the PLC

l

The menu item "Display - Display value" is not set to
"AI

-Out"

à Check values and correct, if necessary

?

Instrument does not appear during connection setup

l

Incorrect termination

à Check termination at the beginning and end points of

the bus and terminate, if necessary, according to the
specification

l

Instrument not connected to the segment

à Check and correct

In Ex applications, the regulations for the wiring of intrinsically
safe circuits must be observed.

?

E

013

l

no measured value available

à sensor in boot phase
à Sensor does not find an echo, e.g. due to faulty

installation or wrong parameter adjustment

à Wrong sensor length entered

?

E

017

l

Adjustment span too small

à Carry out a fresh adjustment and increase the distance

between min. and max. adjustment

?

E

036

l

no operable sensor software

à Carry out a software update or send the instrument for

repair

?

E

042/E043

l

Hardware error, electronics defective

à Exchange instrument or return instrument for repair

?

E

113

l

Communication conflict

à Exchange instrument or return instrument for repair

Fault messages via the
indicating/adjustment
module

40

VEGAFLEX

66 • Foundation Fieldbus

8 Maintenance and fault rectification

32765

-EN

-080716