VEGA VEGAFLEX 66 (-110…+400°C) Foundation Fieldbus User Manual

Page 48

Advertising
background image

Output variable

Output

-

Signal

digital output signal, Foundation Fieldbus
protocol

-

Physical layer

according to IEC 61158-2

Channel Numbers

-

Channel 1

Primary value

-

Channel 2

Secondary value 1

-

Channel 3

Secondary value 2

Transmission rate

31.25 Kbit/s

Current value

10 mA, ±0.5 mA

Accuracy (similar to DIN EN 60770-1)

Reference conditions according to DIN EN 61298-1

-

Temperature

+

18 … +30 °C (+64 … +86 °F)

-

Relative humidity

45 … 75 %

-

Air pressure

860 … 1060 mbar/86 … 106 kPa
(

12.5 … 15.4 psig)

Deviation in characteristics and characteristics

Reference installation conditions

-

Flange size

> DN

100

-

min. distance to installations

>

500 mm (19.69 in)

-

Vessel diameter

1 m (3.281 ft) centrical installaton

-

Medium

Water

Temperature drift (current output)

0.06 %/10 K relating to the max. measuring
range

Accuracy

see diagrams