3 exchange or shorten cable/rod – VEGA VEGAFLEX 62 Foundation Fieldbus User Manual

Page 40

Advertising
background image

Depending on the failure reason and measures taken, the steps
described in chapter "Set up" must be carried out again, if necessary.

8

.3 Exchange or shorten cable/rod

The cable or rod (meas. part) of the probe can be shortened, if
necessary. To loosen the meas. part you need two fork spanners with
spanner width 8.

1

Loosen the measuring component by applying a fork spanner to
the flat surfaces (SW 8), provide counterforce with another fork
spanner (SW 8)

2

Unscrew the loosened measuring component manually

3

Place the enclosed new double washer onto the thread.

Caution:
Make sure that the two components of the double washer remain
together.

4

Screw in a new measuring part manually

5

Exert counterforce with the second fork spanner and tighten the
measuring component on the flat surfaces with a torque of 15 Nm
(11 lbf ft).

Fig. 23: Exchanging the cable or rod

Information:
Please keep the stated torque so that the max. tensile strength
remains.

Reaction after fault rec-
tification

Exchanging the cable/
rod

40

VEGAFLEX

62 • Foundation Fieldbus

8 Maintenance and fault rectification