6 Setup with the integrated display and adjustment unit

PLICSRADIO T62 • Wireless emitting unit (multiple channel)

32624-EN-130228

PLICSRADIO T62 can process measured values of up to three HART

sensors. All measured values are transmitted as digital HART signals

to the same cable (bus). An own, unambiguous address must be

assigned to each connected sensor (HART addr. 1 … 3 corresponds

to input 1 … 3). This mode is also called HART multidrop mode. The

addressing can be carried out directly on each HART sensor via the

respective adjustment unit or a corresponding adjustment software.
Note:

When addresses are being assigned, only one sensor with the same

address must be connected on the bus. If this is not the case, the sen-

sor cannot be accessed and it is not possible to assign an address.

After being switched on, PLICSRADIO T62 first of all carries out a

short self-check. The following steps are carried out:

Internal check of the electronics

indication of the instrument type, firmware version as well as the

instrument TAG (instrument name)

Enquiry of the sensor input

Establishment of a radio connection

The measured value indication displays the digital indication values of

the connected sensors, the measurement loop designation (measure-

ment loop TAG) and the unit. The actual signal strength can be also

displayed. By pushing the [>] key, you move between the individual

indicating windows.

1. By pushing [OK] you move from the measured value indication to

the main menu.

2. Select the menu item "Device settings" with [->] and confirm with

[OK].

You can assign an unambiguous name to PLICSRADIO T62 via the

Device-TAG. This function is recommended when several instruments

are implemented and a good documentation of larger systems is

required.

Enter the requested values via the appropriate keys and save

your settings with [OK].

Set HART address

Switch-on phase

Measured value indica-

tion/Main menu

Device settings - Device-

TAG