8 Maintenance and fault rectification

PLICSRADIO T62 • Wireless emitting unit (multiple channel)

32624-EN-130228

8 Maintenance and fault rectification

8.1 Maintenance

If the instrument is used properly, no special maintenance is required

in normal operation.

8.2 Rectify faults

The operator of the system is responsible for taking suitable meas-

ures to rectify faults.

A maximum of reliability is ensured. Nevertheless, faults can occur

during operation. These may be caused by the following, e.g.:

Measured value from sensor not correct

Voltage supply

Interference on the cables

The first measures to be taken are to check the input and output

signal as well as to evaluate the error messages via the display. The

procedure is described below. Further comprehensive diagnostics

can be carried out on a PC with PACTware and the suitable DTM. In

many cases, the causes can be determined in this way and faults

rectified.

Should these measures not be successful, please call in urgent cases

the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since

we offer this service world-wide, the support is only available in the

English language. The service is free of charge, only the standard

telephone costs will be charged.

Error code Cause

Rectification

No indication

of the signal

strength

Wrong adjustment of

the radio channel

– Adjust transmitter and receiver to the

same radio channel

E008

Sensor not found

– Check connection of the sensor

– Check HART address of the sensor,

addr. 1 … 3 must only be used once

E013

Sensor signals

failure, no valid

measured value

– Check sensor parameter adjustment

– Send sensor for repair

E014

Sensor current

> 21 mA or short-

circuit

– Check sensor, e.g. on failure

– Remove short-circuit

E015

Sensor in boot phase
Sensor current

< 3.6 mA or line

break

– Check sensor, e.g. on failure

– Remove line break

– Check connection of the sensor

E030

Sensor in boot phase
value not valid

– Check sensor parameter adjustment

Reaction when malfunc-

tions occur

Failure reasons

Fault rectification

24 hour service hotline

Error messages via the

display and adjustment

module