VEGA PLICSRADIO T62 Wireless emitting unit User Manual

Page 34

Advertising
background image

34

10 Supplement

PLICSRADIO T62 • Wireless emitting unit (multiple channel)

32624-EN-130228

Ʋ Housing socket

– 3 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm)

or:

– 3 x closing cap ½ NPT

Ʋ Electronics housing

– 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm), 1 x

antenna connection (R-SMA)

or:

– 1 x closing cap ½ NPT, 1 x antenna connection

(R-SMA)

Spring-loaded terminals

for wire cross-section up to 2.5 mm² (AWG 14)

Ambient conditions
Ambient, storage and transport tempera-

ture

-40 … +80 °C (-40 … +176 °F)

Electrical protective measures
Protection rating

Ʋ Plastic housing

IP 66/IP 67

Ʋ Aluminium housing

IP 66/IP 67

3)

Overvoltage category

III

Protection class depending of the power supply unit version

Ʋ 24 V version

II

Ʋ 115/230 V version

I

Electrical separating measures
Reliable separation according to VDE 0106 part 1 between power supply and input

Ʋ Reference voltage

253 V (50 V at 24 V power supply unit version)

Ʋ Isolation resistance

3.75 kV (1.5 kV with 24 V version of the power supply

unit)

Radio approvals
Radio approvals

Ʋ Standard version

FCC ID: OUR-24xSTREAM

Ʋ Version increased range

FCC ID: OUR-9xSTREAM

IC (Industry Canada)

Ʋ Standard version

4214A 12008

Ʋ Version increased range

4214A-9xSTREAM

Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments have to be carefully

noted. They are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools"

and "serial number search" as well as via "Downloads" and "Approvals".

3)

A suitable cable is the prerequisite for maintaining the protection rating.

Advertising