3 function chart – VEGA VEGACAP 27 - Relay (DPDT) User Manual

Page 15

Advertising
background image

15

6 Setup

VEGACAP 27 • - Relay (DPDT)

33758-EN-130916

3. Turn the below potentiometer (6) first of all anticlockwise (max. 20

turns) until the control lamp signals "covered".
Mode A (overfill protection) = control lamp lights
Mode B (dry run protection) = control lamp extinguishes
If this condition is already reached, you can continue with the next

step.

4. Turn the potentiometer (6) very slowly (due to the damping) clock-

wise until the control lamp signals "uncovered".
Mode A (overfill protection) = control lamp extinguishes
Mode B (dry run protection) = control lamp lights

5. Turn the potentiometer (6) clockwise according to the following

chart.

6. The probe is now ready for operation.

Sensitivity

Standard

very sensitive

additional turns

Dielectric constant >2
= 2 turns

Dielectric constant >1.5
= 1 turn

Tab. 1: Number of additional turns for the potentiometer (6)

Note:

With the measurement of products with very low dielectric values, the

number of turns can be reduced up to 1 according to the chart.
This setting is too sensitive with conductive, adhesive products.
Note:

When placing the housing cover, make sure that the inspection glass

is above the signal lamp of the electronics module.

6.3 Function chart

The following chart provides an overview of the switching conditions

depending on the set mode and the level.

Level

Switching status Control lamp

Mode A
Overflow protec-

tion

5

3

4

(8)

(6) (7)

Relay energized

Mode A
Overflow protec-

tion

5

3

4

(8)

(6) (7)

Relay deener-

gized