VEGA VEGACAP 27 - Relay (DPDT) User Manual

Page 26

Advertising
background image

26

9 Supplement

VEGACAP 27 • - Relay (DPDT)

33758-EN-130916

Ʋ Single chamber housing

– 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm),

1 x blind plug M20 x 1.5; attached 1 x cable entry

M20 x 1.5

or:

– 1 x cable entry ½ NPT, 1 x blind plug ½ NPT, 1 x cable

entry ½ NPT

or:

– 1 x plug M12 x 1; 1 x blind plug M20 x 1.5

Screw terminals

for wire cross-section up to 1.5 mm² (AWG 16)

Adjustment elements
Mode switch

Ʋ A

Min. detection or dry run protection

Ʋ B

Max. detection or overflow protection

Potentiometer

Switching point adaptation

Voltage supply
Operating voltage

20 … 253 V AC, 50/60 Hz, 20 … 72 V DC (at

U >60 V DC, the ambient temperature can be max.

50 °C/122 °F)

Power consumption

1 … 9 VA (AC), approximately 1.5 W (DC)

Electrical protective measures
Protection rating

IP 66/IP 67

Overvoltage category

III

Protection class

I

Approvals
Instruments with approvals can have different technical data depending on the version.
For that reason the associated approval documents of these instruments have to be carefully

noted. They are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools"

and "serial number search" as well as via "Downloads" and "Approvals".

Advertising