7 Maintenance and fault rectification

VEGACAP 27 • - Relay (DPDT)

33758-EN-130916

6

7

4

3

CPH

CM

2 MΩ

2 MΩ

2 MΩ

3

2

1

Fig. 21: Check the resistance in the probe
1 Contact 1 (middle pin)

2 Variable capacitor (phase)

3 Capacitor

Measure the resistance values between the following contacts with an

ohmmeter (range MΩ).
Contact 4 against contact 1 (middle pin)

The resistor must be 2 MΩ.
If the resistor is lower, this means moisture in the housing or a fault in

the electrode insulation. A possible reason could be also a non-insu-

lated electrode which is used in a conductive (humid) medium.
If the resistor is higher or if the connection is interrupted, the reason is

mostly a contact error in the adapter plate or a defective resistor due

to strong electrostatic arking.
In both cases, the probe must be repaired in our premises.
Contact 4 against vessel

The electrical connection between contact 4 and metal vessel (not

the mounting boss or probe flange) should good. Measure the resist-

ance value between contact 4 and vessel with an ohmmeter (range

very small).

Shortcircuit (0 … 3 Ω) - optimum connection

Resistor > 3 Ω - bad connection