7 Maintenance and fault rectification

VEGACAP 27 • - Relay (DPDT)

33758-EN-130916

Error

Cause

Rectification

– The instrument

signals covered

without cover-

ing with the

medium

– The instrument

signals covered

with cover-

ing with the

medium

Wrong mode se-

lected

Set the correct mode on the mode

switch (A - overflow protection, B - dry

run protection). Wiring should be car-

ried out according to the quiescent

current principle.

Operating voltage

too low

Check operating voltage

Shortcircuit in the

probe, e.g. be-

cause of moisture

in the housing

Remove the electronics module.

Check the resistance between the

marked plug connections. See the fol-

lowing instructions.

Electronics de-

fective

Press the mode switch (A/B). If the in-

strument then changes the mode, the

instrument may be mechanically dam-

aged. Should the switching function in

the correct mode still be faulty, return

the probe for repair.
Push the mode switch. If the probe

then does not change the mode, the

electronics module may be defective.

Exchange the electronics module.

Remove the electronics module. Check the resistance between the

two plug connections.
There must no longer be a connection (high impedance). If there is

still a connection - exchange the instrument or return it for repair

Checking the switching

signal

Check the resistance in

the probe