P

robes in coax version require no gating out of false echoes since they

are not influenced by false reflections.

G

ating out of false signals

C

hange now?

P

roceed as follows:

1

M

ove from the measured value display to the main menu by

pushing [OK].

2

S

elect the menu item "Service" with [->] and confirm with [OK].

N

ow the menu item "False signal suppression" is displayed.

3

C

onfirm "False signal suppression - Change now" with [OK] and

select in the below menu "Create new". Enter the actual distance
from the sensor to the product surface. All false signals in this area
are detected by the sensor and saved after confirming with [OK].

Note:
C

heck the distance to the product surface, because if an incorrect (too

large) value is entered, the existing level will be saved as false signal.
T

he filling level would then no longer be detectable in this area.

T

his function enables reading out parameter adjustment data as well

as writing parameter adjustment data into the sensor via the indicating
and adjustment module. A description of the function is available in the
operating instructions manual "Indicating and adjustment module".

T

he following data are read out or written with this function:

l

M

easured value presentation

l

A

djustment

l

M

edium

l

V

essel form

l

D

amping

l

L

inearisation curve

l

S

ensor-TAG

l

D

isplayed value

l

D

isplay unit

l

S

caling

l

C

urrent output

l

U

nit of measurement

l

L

anguage

l

S

ensitivity

T

he following safety-relevant data are not read out or written:

l

HART

mode

l

PIN

l

SIL

l

S

ensor length/Sensor type

Copy sensor data

VEGAFLEX

66 • 4 … 20

mA/HART two-wire