VEGA VEGAFLEX 66 (-200…+400°C) 4 … 20 mA_HART two-wire User Manual

Page 43

Advertising
background image

Error

Cause

Removal

4 … 20

mA signal

not stable

L

evel fluctuations Set damping via the indicating and

adjustment module

4 … 20

mA signal

missing

E

lectrical con-

nection faulty

C

heck connection according to chap-

ter "

Connection steps

"

and if ne-

cessary, correct according to chapter
"

Wiring plan

"

V

oltage supply

missing

C

heck cables for breaks; repair if

necessary

O

perating voltage

too low or load
resistance too
high

C

heck, adapt if necessary

C

urrent signal

greater than 22 mA
or less than
3.6

mA

O

scillator in the

sensor defective

E

xchange the instrument or send it in

for repair

I

n Ex applications, the regulations for the wiring of intrinsically safe

circuits must be observed.

T

he indicating and adjustment modules indicates faults via error codes

and text messages. The following table describes the error codes with
status according to NE 107 and gives information on the causes of
failure and their removal:

Status accor-
ding to NE 107

Error code

Text message

Cause/Rectification

F

ailure

E

013

no measured value available

S

ensor in boot phase

no measured value available

S

ensor does not find an echo, e.g.

due to faulty installation or wrong
parameter adjustment

no measured value available

W

rong sensor length entered

E

017

A

djustment span too small

A

djustment not within the specifica-

tion. Carry out the adjustment again,
increasing the distance between
min. and max. adjustment

E

036

N

o operable software

F

ailed or interrupted software up-

date/Repeat software update

E

042

H

ardware error, electronics defec-

tive

E

xchange the instrument or send it

in for repair

Error messages via the
indicating and adjust-
ment module

VEGAFLEX

66 • 4 … 20

mA/HART two-wire

43

8 M

aintenance and fault rectification