Status accor-
ding to NE 107

Error code

Text message

Cause/Rectification

E

043

H

ardware error, electronics defec-

tive

E

xchange the instrument or send it

in for repair

D

epending on the failure reason and measures taken, the steps

described in chapter "Set up" must be carried out again, if necessary.

8

.3 Exchanging the electronics module

I

f the electronics module is defective, it can be replaced by the user.

I

n Ex applications only one instrument and one electronics module with

respective Ex approval may be used.

I

f there is no electronics module available on site, one can be ordered

from the VEGA agency serving you.

T

he new electronics module must be loaded with the settings of the

sensor. These are the options:

l

A

t the factory by VEGA

l

O

r on site by the user

I

n both cases, the sensor serial number is necessary. The serial

numbers are stated on the type label of the instrument, inside the
housing or on the delivery note.

Information:
W

hen loading on site, first of all the order data must be downloaded

from the Internet (see operating instructions manual "Oscillator").

T

he electronics modules are adapted to the respective sensor and

distinguish also in the signal output or power supply.

E

lectronics module FX-E.60H suitable for VEGAFLEX 61, 62, 63, 65,

66 - 4 … 20

mA/HART:

l

FX-E.

60HX (X =

without approvals)

l

FX-E.

60HA (A =

approvals CA, DA according to product list)

l

FX-E.

60HC (C =

approvals XM, CX, CM, CK, CI, DX, DM, DI, GX,

UX, UF

according to product list)

8

.4 Software update

T

he software version of VEGAFLEX 66 can be determined as follows:

l

on the type label of the electronics

l

via the indicating and adjustment module

Reaction after fault rec-
tification

Sensor serial number

Assignment

4

… 20 mA/HART

44

VEGAFLEX

66 • 4 … 20

mA/HART two-wire

8 M

aintenance and fault rectification

34173

-EN

-100427

Advertising