VEGA VEGAPULS 66 (≥ 2.0.0 - ≤ 3.8) enamel Foundation Fieldbus User Manual

Page 20

Advertising
background image

100%

0%

1

> 500 mm

Fig. 13: VEGAPULS 66 in a bypass tube. The polarisation marking on the
process fitting must be in one plane with the tube holes or the tube connection
openings.

1

Marking of the polarisation direction

When the sensor is mounted on a bypass tube, the distance from
VEGAPULS

66 to the upper tube connection should be approx.

500 mm (19.69 in) or more. In case of extremely rough tube inner
walls, you should use an inserted tube (tube in tube) or a radar sensor
with tube antenna.

Information:
With VEGAPULS 66 in flange version, the polarisation plane is always
in the center between two flange holes.

20

VEGAPULS

66 enamel • Foundation Fieldbus

4 Mounting

33336

-EN

-090305

Advertising