VEGA VEGAPULS SR 68 4 … 20 mA_HART two-wire User Manual

Page 41

Advertising
background image

41

6 Set up with the display and adjustment module

VEGAPULS SR 68 • 4 … 20 mA/HART two-wire

38294-EN-130624

You can find in the operating instructions manual "Display and adjust-

ment module" also the description of the menu sections "Display" and

"Info".
In the main menu point "Setup", the individual submenu points should

be selected subsequently and provided with the correct parameters

to ensure the optimum adjustment of the measurement. The proce-

dure is described in the following.
Setup
Each medium has different reflection properties. With liquids, further

interfering factors are fluctuation product surface and foam genera-

tion. With bulk solids, these are dust generation, material cone and

additional echoes from the vessel wall.
To adapt the sensor to these different measuring conditions, the

selection "Liquid" or "Bulk solid" should be made in this menu item.

Through this selection, the sensor is adapted perfectly to the product

and measurement reliability, particularly in products with poor reflec-

tive properties, is considerably increased.
Enter the requested parameters via the appropriate keys, save your

settings with [OK] and jump to the next menu item with the [ESC] and

the [->] key.

In addition to the medium, also the application, i.e. the measuring site,

can influence the measurement.
With this menu item, the sensor can be adapted to the applications.

The adjustment possibilities depend on the selection "Liquid" or "Bulk

solid" under "Medium".

The following options are available when "Liquid" is selected:

Setup - Medium

Setup - Application

Advertising