6 Set up with the display and adjustment module

VEGAPULS SR 68 • 4 … 20 mA/HART two-wire

38294-EN-130624

If a false signal suppression has already been created in the sensor,

the following menu window appears when selecting "False signal

suppression":

The menu item "Delete" is used to completely delete an already cre-

ated false signal suppression. This is useful if the saved false signal

suppression no longer matches the metrological conditions in the

vessel.
The menu item "Extend" is used to extend an already created false

signal suppression. This is useful if a false signal suppression was

carried out with a too high level and not all false signals could be de-

tected. When selecting "Extend", the distance to the product surface

of the created false signal suppression is displayed. This value can

now be changed and the false signal suppression can be extended to

this range.

With the function "Echo curve memory" the echo curve can be saved

at the time of setup. This is generally recommended; for using the As-

set Management functions it is absolutely necessary. If possible, the

curve should be saved with a low level in the vessel.
With the adjustment software PACTware and the PC, the high resolu-

tion echo curve can be displayed and used to recognize signal

changes over the operating time. In addition, the echo curve of the

setup can be also displayed in the echo curve window and compared

with the actual echo curve.

A linearization is necessary for all vessels in which the vessel volume

does not increase linearly with the level - e.g. a horizontal cylindri-

cal or spherical tank - and the indication or output of the volume is

required. Corresponding linearization curves are preprogrammed

for these vessels. They represent the correlation between the level

percentage and vessel volume.
By activating the appropriate curve, the volume percentage of the

vessel is displayed correctly. If the volume should not be displayed in

percent but e.g. in l or kg, a scaling can be also set in the menu item

"Display".

Diagnostics - Echo curve

memory

Additional adjustments -

Linearization curve