.6 Result of the recurring function test

If all test points could be terminated successfully, then the recurring
function test was successful.

Fulfilled test points

3.1 / 3.2 / 3.3 / 3.4 / 3.5

Fault detection rate λ

du

96 %

3.1 / 3.2 / 3.5 (sensor documentation
of the setup or a sensor documenta-
tion which is at least 6 months old, is
not available)

Fault detection rate λ

du

88 %

The test must be repeated in regular intervals. The time periods
depend on the PFD

avg

value according to the sepcifications in the

Safety Manual (SIL).

If one of the test points (3.1 / 3.2 / 3.5) could not be terminated
successfully, there is probably an undetected dangerous failure. The
recurring function test has failed.

In this case, proof of functional safety can only be provided by moving
the level to the switching point.

Function test successful

Function test not suc-
cessful

14

Recurring function test • for VEGAPULS series 60

3 Sequence of the recurring function test