VEGA VEGAPULS series 60 Recurring function test User Manual

Page 16

Advertising
background image

□ Sensor documentation of the
setup available
or

□ Sensor documentation (at least 6
months old) is available

File name:

□ Parameters correspond

□ Parameters do not correspond -
however checked on correctness

File name:

□ Parameters do not correspond -
deviation not acceptable

File name:

□ Sensor documentation of the
setup not available

□ Parameters checked on correct-
ness and saved (recheck after 6
months necessary)

File name:

Test result

□ All parameters correct or
checked on correctness

□ Parameters not correct

Tester:

Test 3.4 - Verification of the echo data

No false echoes or echoes with
useful echo probability 0 %

□ Corresponds

□ Does not correspond

Corresponding amplitude

□ In the tolerance range

□ Not in the tolerance range

Test result

□ Corresponds

□ Does not correspond

Test 3.5 - Verification of the sensor reaction

Reduction of the level

□ Distance value [m] increases

□ Other reaction

Increase of the level

□ Distance value [m] decreases

□ Other reaction

Test result

□ Corresponding sensor reaction

□ Sensor reaction does not corre-
spond

Summary 96 % (λ

du

)

Date

Signature

Test 3.1 / 3.2 / 3.3 / 3.4 / 3.5

□ All five test points passed

□ One or several test points did not
pass

Summary 88 % (λ

du

)

Date

Signature

16

Recurring function test • for VEGAPULS series 60

4 Test protocol - Recurring function test

36553

-EN

-100225