4 test protocol – recurring function test, 4test protocol - recurring function test – VEGA VEGAPULS series 60 Recurring function test User Manual

Page 15

Advertising
background image

4

Test protocol - Recurring function test

If you copy this protocol, please note the date of the function test, the
measurement loop and the sensor serial number on each page.

Specifications VEGAPULS

Tester

Measurement loop name (sensor-TAG)

Sensor type

Serial number of the sensor

Software version

Required plant situation (according to chapter 2.4)

□ maintained

Safety-instrumented system (SIS)

□ yes

SIL activated

□ yes

Medium or product group

Date of the setup (sensor documentation)

Date of the last function test (if carried out)

Test 3.1 - Restart of the sensor

Measured value before switching off Current value min. in mA

Current value max. in mA

Measured value after switching on
again

Current value min. in mA

Current value max. in mA

Difference of the current values

Current value min. in mA

Current value max. in mA

Duration of the inspection in s

Test result
Min. and max. values

□ Deviation ≤ 2 %
(test point successful)

□ Deviation > 2 %
(test point not successful)

Test 3.2 - Verification of the current output

Lower simulation value (4 mA)

Indication mA-meter in mA

Intermediate result ≤ 2 % (≤0.32 mA) □ Corresponds

□ Does not correspond

Upper simulation value (20 mA)

Indication mA-meter in mA

Intermediate result ≤ 2 % (≤0.32 mA) □ Corresponds

□ Does not correspond

Test result - Total

□ Corresponds

□ Does not correspond

Recurring function test • for VEGAPULS series 60

15

4 Test protocol - Recurring function test

36553

-

EN

-100225

Advertising