Information:
Document the recurring function test, for example, in the test protocol
in the supplement.

The following conditions must be fulfilled when performing the
recurring function test:

0

dB

1

2

Fig. 1: Level echo - VEGAPULS
1

Amplitude of the useful echo above the noise level (signal/noise ratio)

2

Noise level

l

The level must be in the following areas:

-

Min. distance to the level: Lower antenna edge +200 mm

-

Level above the vessel bottom ≥ 250 mm

-

Reliability at least 20 dB (amplitude of the useful logarithmic
echo above the noise level). The reliability can be verified
during the test.

l

The process conditions must be nearly constant (level, process
pressure, process temperature).

l

The medium must be the same as during setup or the medium
must at least belong to the same product group

-

Solvents/Liquid gases/Hydrocarbons/Oils (DK value < 3)

-

Chemical mixtures (DK value 3 … 10)

-

Water/Acids/Bases (DK value > 10 or conductive)

6

Recurring function test • for VEGAPULS series 60

2 Prerequisites

36553

-EN