7 setup, 1 adjustment system, 2 connect the pc – VEGA PLICSMOBILE T61 User Manual

Page 23

Advertising
background image

23

7 Setup

PLICSMOBILE T61 • External GSM/GPRS radio unit

37700-EN-130228

7 Setup

7.1 Adjustment system

A pC with PACTware and respective DTM is required for setup. The

connection is carried out via a standard mini USB cable (in the scope

of delivery). A released SIM card with data transmission option must

be used in PLICSMOBILE T61. A good network coverage of the used

GSM/GPRS network must be available at the place of operation.
Adjustment on the instrument is limited to a test key and an LED. With

these, the operation and the status of the instruments can be checked

(selection of the GSM network, standby …).

4

1

3

2

USB

Status

Test

SIM-Card

Fig. 10: Display and adjustment elements
1 SIM card slot

2 Status indication

3 Key to the test operation

4 Mini-USB interface

Information:

The function description of the key and the status indication is avail-

able in chapter "Mobile phone network and SIM card".

7.2 Connect the PC

The parameter adjustment of PLICSMOBILE T61 is carried out via

PC and USB interface. The required connection is located in the

electronics housing. Keep in mind that proper functioning of the USB

interface can only be guaranteed in the (limited) temperature range of

0 … +60 °C.
If the PC is provided with a Full-Power-USB-Port, the PLICSMOBILE

is powered via the integrated USB power supply. Parameter adjust-

ment is thus possible without connected power supply, but measured

value recording and transmission is not possible. Power supply via

USB is not possible with a Low-Power-USB-Port.
Note:

The connection via USB requires a driver. First install the driver before

connecting PLICSMOBILE T61 to the PC.
The required USB driver is included on the CD "DTM Collection". You

should always use the latest version to ensure support of all instru-

Setup requirements