4 Mounting

VEGADIF 65 • Profibus PA

36129-EN-130417

+

1

2

4

3

Fig. 16: Measurement setup with flow measurement of gases, connection via

3-fold valve block
1 VEGADIF 65

2 3-fold valve block

3 Blocking valves

4 Orifice or impact pressure probe

+

1

2

3

Fig. 17: Measurement setup with flow measurement of gases, connection via

3-fold valve block, flanging on both sides
1 VEGADIF 65

2 3-fold valve block, flanging on both sides

3 Orifice or impact pressure probe

1. Mount VEGADIF 65 below the measurement loop
2. Mount condensate vessels at the same height with the discharge

socket and at the same distance to VEGADIF 65

3. Fill the effective pressure lines to the height of the condensate

vessels before setup

In vapours