6 Set up with the display and adjustment module PLICSCOM

VEGABAR 54 • 4 … 20 mA

36725-EN-130321

The display and adjustment module enables the adjustment without

filling or pressure. Thanks to this, you can carry out your settings

already in the workshop without the instrument having to be installed.
The actual measured value is displayed in addition to the menu items

for zero/span adjustment.

VEGABAR 54 is preset to application "Level measurement". Proceed

as follows when switching over to application "Process pressure

measurement":
1. Push the [OK] button in the measured value display, the menu

overview is displayed.

2. Select the menu "Service" with [->] and confirm with [OK].

Basic adjustment
Display
Diagnostics

Service
Info

3. Select the menu item "Application" with [->] and edit with [OK].

Warning:

Note the warning: "Output can change".
4. Select with [->] "OK" and confirm with [OK].
5. Select "Process pressure" from the list and confirm with [OK].

In this menu item you select the adjustment unit as well as the unit for

the temperature indication in the display.
To select the adjustment unit (in the example switching over from bar

to mbar), proceed as follows:

3)

1. Push the [OK] button in the measured value display, the menu

overview is displayed.

Basic adjustment
Display
Diagnostics
Service
Info

2. Confirm the menu "Basic adjustment" with [OK], the menu item

"Unit" will be displayed.

Unit
Unit of measurement
bar

Temperature unit
°C

3. Activate the selection with [OK] and select "Units of measure-

ment with [->].

4. Activate the selection with [OK] and select the requested unit with

[->] (in the example mbar).

5. Confirm with [OK] and move to position correction with [->].

Select application "Pro-

cess pressure measure-

ment"

Select unit

3)

Selection options: mbar, bar, psi, Pa, kPa, MPa, inHg, mmHg, inH

2

O,

mmH

2

O.