8 Maintenance and fault rectification

VEGABAR 54 • 4 … 20 mA

36725-EN-130321

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

(+ F

a

)

2

)

With:

F

total

: Total deviation

F

perf

: Basic accuracy

F

stab

: Long-term drift

F

T

: Temperature coefficient (influence of medium or ambient

temperature)

F

Kl

: Deviation

F

a

: Error current output

Pressure measurement in the pipeline 8 bar (800 KPa)
Product temperature 50 °C, reference temperature 20 °C
Calculation ΔT: ΔT = 50 °C - 20 °C = 30 K
VEGABAR 54, with measuring range 25 bar, version 0.2 %
Calculation of the set Turn Down: TD = 25 bar/8 bar, TD = 3.1
Basic accuracy digital output signal in percent:

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

)

F

T

= (0.1 %/10 K x ΔT)

F

Kl

= 0.2 %

F

perf

= √((0.1 %/10 K x 30 K)

2

+ (0.2 %)

2

)

F

perf

= 0.36 %

Total deviation digital output signal in percent:

F

total

= F

perf

+ F

stab

F

stab

= (0.1 % x TD)/year

F

stab

= (0.1 % x 3.1)/year

F

stab

= 0.31 %

F

total

= 0.36 % + 0.31 % = 0.67 %

Total deviation digital output signal absolute:

F

total

= 0.67 % x 8 bar/100 % = 53.6 mbar

Basic accuracy analogue output signal in percent:

F

perf

= √((F

T

)

2

+ (F

Kl

)

2

+ (F

a

)

2

)

F

T

= (0.1 %/10 K x ΔT)

F

Kl

= 0.2 %

F

a

= 0.15 %

F

perf

= √((0.1 %/10 K x 30 K)

2

+ (0.2 %)

2

+ (0.15 %)

2

)

F

perf

= 0.39 %

Total deviation analogue output signal in percent:

F

total

= F

perf

+ F

stab

F

stab

= (0.1 % x TD)/year

F

stab

= (0.1 % x 3.1)/year

F

stab

= 0.31 %

F

total

= 0.39 % + 0.31 % = 0.70 %

Example