8 Maintenance and fault rectification

VEGABAR 51 • 4 … 20 mA/HART

36713-EN-130321

Error code Cause

Rectification

4 … 20 mA

signal not

stable

Level fluctuations

– Set the integration time via the

display and adjustment module or

PACTware

No atmospheric pres-

sure compensation

– Check the pressure compensation

in the housing and clean the filter

element, if necessary

4 … 20 mA

signal miss-

ing

Connection to volt-

age supply wrong

– Check connection according to

chapter "Connection steps" and

if necessary, correct according to

chapter "Wiring plan"

No power supply

– Check cables for breaks; repair if

necessary

Operating voltage

too low or load resist-

ance too high

– Check, adapt if necessary

Current sig-

nal greater

than 22 mA

or less than

3.6 mA

Electronics module

or measuring cell de-

fective

– Exchange the instrument or send it

in for repair

In Ex applications, the regulations for the wiring of intrinsically safe

circuits must be observed.

Error code Cause

Rectification

E013

no measured value

available

8)

– Exchange the instrument or send it

in for repair

E017

Adjustment span too

small

– repeat with modified values

E036

no operable sensor

software

– Carry out a software update or send

instrument for repair

E041

Hardware error

– Exchange the instrument or send it

in for repair

Depending on the reason for the fault and the measures taken, the

steps described in chapter "Set up" may have to be carried out again.

8.3 Exchanging the electronics module

In case of a defect, the electronics module can be exchanged by the

user against an identical type. If no electronics module is available on

side, the module can be ordered from the agency serving you.
Ordering and exchange are possible with or without sensor serial

number. The electronics module with serial number includes order-

specific data such as factory setting, seal material etc. These are not

included in the electronics module without serial number.

Error messages via the

display and adjustment

module

Reaction after fault recti-

fication

8)

Fault message can also appear if the pressure is higher than the nominal

range.