Abb total flow – VEGA VEGABAR 82 Modbus and Levelmaster protocol - Operating Instructions User Manual

Page 79

Advertising
background image

79

10 Supplement

VEGABAR 82 • Modbus and Levelmaster protocol

46294-EN-131107

ABB Total Flow

Wiring plan

+

+

power suppl

y

MODBUS

D0

D1

IS GND

US

B

1

2

13

45

2o

ff

on

(

)

(

)

(-)

(-)

8

1

2

6

7

Bus +

Bus -

GND

VBAT

Fig. 38: Connection of VEGABAR 82 to RTU ABB Total Flow
1 VEGABAR 82

2 RTU ABB Total Flow

Parameter

Parameter

Value

Baud Rate

9600

Floating Point Format Code

0

RTU Data Type

16 Bit Modicon

Input Register Base Number

1

The basic number of the input registers is always added to the input register address of VEGABAR

82.
Address 1303 must hence be entered as register address for 1302 for RTU ABB Total Flow.

Advertising