7 dimensions, Scadapack – VEGA VEGABAR 82 Modbus and Levelmaster protocol - Operating Instructions User Manual
Page 82
Advertising
82
10 Supplement
VEGABAR 82 • Modbus and Levelmaster protocol
46294-EN-131107
ScadaPack
Wiring plan
+
+
power supply
MODBU
S
D0
D1
IS GND
US
B
1
3
2
13
45
5
2
1
3
4
9
6
7
8
2o
ff
on
(
)
(
)
(-)
(-)
+8
+30 Vdc
to
GND
COM Part 3 (C3)
RS485
TXD-
TXD+
GND
Fig. 41: Connection of VEGABAR 82 to RTU ScadaPack
1 VEGABAR 82
2 RTU ScadaPack
3 Voltage supply
Parameter
Parameter
Value
Baud Rate
9600
Floating Point Format Code
0
RTU Data Type
Floating Point
Input Register Base Number
30001
The basic number of the input registers is always added to the input register address of VEGABAR
82.
Address 31303 must hence be entered as register address for 1302 for RTU ScadaPack.
10.7 Dimensions