4 Mounting
External housing • For pressure transmitter VEGABAR series 80
45081-EN-131119
1. Mark the holes according to the following drilling template
2. Depending on the mounting surface, fasten the wall mounting
plate with 4 screws
90 mm
(3.54")
R 3,5 mm
(0.14"
)
3mm
(0.12")
70 mm
(2.76")
8 mm
(0.32")
93 mm (3.66"
)
110 mm (4.33"
)
Fig. 5: Hole pattern - wall mounting plate (external housing)
Tip:
Mount the wall mounting plate in such a way that the cable gland of
the base points downward. Rain and condensation water can thus
drain off.
The base of stainless steel can be displaced in 90° increments on the
wall mounting plate, the base of plastic by 180°.
Turn the cable gland of the electronics housing downward. The hous-
ing can be turned by 330° without the use of any tools.
Warning:
With the plastic housing, the four screws of the base may only be
screwed in hand tight. Exceeding the max. torque specified in chapter
"Technical data" can damage the wall mounting plate.
Wall mounting - External
housing