17

5 Connecting to power supply

VEGASWING 66 • - transistor (NPN/PNP)

44951-EN-130805

5 Connecting to power supply

5.1 Preparing the connection

Always keep in mind the following safety instructions:

Connect only in the complete absence of line voltage

In hazardous areas you must take note of the respective regulations,

conformity and type approval certificates of the sensors and power

supply units.
Only use metal housings (aluminium, stainless steel). The plastic

housing is not permitted.

Connect the operating voltage according to the following diagrams.

Take note of the general installation regulations. As a rule, connect

VEGASWING 66 to vessel ground (PA), or in case of plastic vessels,

to the next ground potential. On the side of the instrument housing

there is a ground terminal between the cable entries. This connection

serves to drain off electrostatic charges. In Ex applications, the instal-

lation regulations for hazardous areas must be given priority.
The data for power supply are specified in chapter "Technical data".

Use two-wire, screened cable. Connect the cable screen on both

ends to ground potential. In the sensor, the screen must be connected

directly to the internal ground terminal. The ground terminal on the

outside of the housing must be connected to the potential equalisa-

tion (low impedance).
Use cable with round cross section for instruments with housing and

cable gland. To ensure the seal effect of the cable gland (IP protection

rating), find out which cable outer diameter the cable gland is suitable

for.

5 … 9 mm (0.20 … 0.35 in)

6 … 12 mm (0.24 … 0.47 in)

10 … 14 mm (0.40 … 0.55 in)

Use a cable gland fitting the cable diameter.
In hazardous areas, only use approved cable connections for VEGAS-

WING 66.

Take note of the corresponding installation regulations for Ex applica-

tions.
Cover all housing openings conforming to standard according to

EN 60079-1.

5.2 Connection procedure

With Ex instruments, the housing cover may only be opened if there is

no explosive atmosphere present.
Proceed as follows:
1. Unscrew the housing cover
2. Loosen compression nut of the cable entry

Note safety instructions

Take note of safety

instructions for Ex

applications

Voltage supply

Connection cable

Connection cable

for Ex applications