3 function chart – VEGA VEGASWING 66 - transistor (NPN-PNP) With SIL qualification User Manual

Page 23

Advertising
background image

23

6 Setup

VEGASWING 66 • - transistor (NPN/PNP)

44951-EN-130805

(max. - maximum detection or overflow protection, min. - minimum

detection or dry run protection).

With this DIL switch (5) you can set the switching point to liquids

having a density between 0.5 and 0.7 g/cm³ (0.018 and 0.025 lbs/

in³). With the basic setting, liquids with a density of ≥ 0.7 g/cm³ (0.025

lbs/in³) can be detected. In liquids with lower density, you must set

the switch to ≥ 0.5 g/cm³ (0.018 lbs/in³). The specifications for the

position of the switching point relate to water - density value 1 g/cm³

(0.036 lbs/in³). In products with a different density, the switching point

will shift in the direction of the housing or tuning fork end depending

on the density and type of installation.
Note:

Keep in mind that foams with a density > 0.45 g/cm³ (0.016 lbs/in³)

are detected by the sensor. This can lead to erroneous switchings,

particulary when the sensor is used for dry run protection.
Note:

In case of strong boiling or deployment processes as well as extreme

outgasing, the density of the gas/product mixture on the product

surface can be so low that it can be no longer detected by the sensor.

This can cause faulty switchings.

6.3 Function chart

The following chart provides an overview of the switching conditions

depending on the set mode and the level.

Level

Switching sta-

tus

Signal lamp -

green
Voltage supply

Signal lamp -

yellow
Switching sta-

tus

Signal lamp

- red
Fault message

Mode max.
Overflow pro-

tection

closed

Mode max.
Overflow pro-

tection

open

Mode min.
Dry run protec-

tion

closed

Mode min.
Dry run protec-

tion

open

Sensitivity adjustment (5)