VEGA FIBERTRAC 31 Foundation Fieldbus User Manual

Page 35

Advertising
background image

35

6 Set up with the display and adjustment module

FIBERTRAC 31 • Foundation Fieldbus

41780-EN-131119

Caution:

Independent of the selected reference value, the relay will deenergize

in case of failure.

With this menu item you safeguard the sensor parameters against

unauthorized or unintentional modifications.
This menu item is described in the operating instructions manual

"Display and adjustment module".
Display

With this parameter you can change the display language.

This parameter is described in the operating instructions manual

"Display and adjustment module".

With this parameter you can change the indication of the display.

You can choose if the display should show the actual pulse rate, the

electronics temperature or the percentage value.

Diagnostics
In this menu item, you can enquire the status of your sensor. In normal

operation, the sensor displays the message "OK". In case of fault, you

will find the corresponding fault code here.
This parameter is described in the operating instructions manual

"Display and adjustment module".

The peak value function holds the max. and min. values during opera-

tion.
This parameter is described in the operating instructions manual

"Display and adjustment module".

Here you can retrieve the adjustment value of the sensor. This is the

percentage value of the difference of the min. and max. adjustment

points (Delta I). The value is an indication for the reliability and repro-

ducibility of the measurement.
The higher the difference between the two adjustment points,

the higher the differential value (Delta I) and the more reliable the

measurement. A Delta I value below 10 % is an indication for a critical

measurement.
To increase the Delta I value, you have to increase the distance of the

min. and max. adjustment points in the linearization.

Lock setup - adjustment

Display - Language

Display - Displayed value

Diagnostics - Device

status

Diagnosis - Peak value

Diagnosis - Adjustment

data