6 Set up with the display and adjustment module

FIBERTRAC 31 • Foundation Fieldbus

41780-EN-131119

Setup: Settings, e.g. for measurement loop name, isotope, applica-

tion, background radiation, adjustment, signal output
Display: Settings, for example language, measured value display
Diagnosis: Information, for example, of device status, peak value,

simulation
Additional adjustments: Instrument unit, reset, date/time, copying

function
Info: Instrument name, hardware and software version, date of manu-

facture, instrument features

Check if the correct language is already set for the display. If not, you

can change the language in the menu item "Display/Language".

Start with the setup of FIBERTRAC 31.
In the main menu point "Setup", the individual submenu points

should be selected one after the other and provided with the correct

parameters to ensure optimum adjustment of the measurement. The

procedure is described in the following.
Stick with the normal sequence of the menu items as closely as pos-

sible.
Setup
In this menu item you can adjust the FIBERTRAC 31 to the integrated

isotope in the source container.
For this purpose, check which isotope is integrated in the source

container. You can find this information on the type label of the source

container.

With this selection, the sensitivity of the sensor is adapted in an opti-

mum way to the isotope.
The FIBERTRAC 31 requires this information for the decay compen-

sation. An annual recalibration is hence not necessary.
Enter the requested parameters via the appropriate keys, save your

settings with [OK] and jump to the next menu item with the [ESC] and

the [->] key.

Enter here, the respective application.

Procedure

Setup - Isotope

Setup - Application