6 Set up with the display and adjustment module

FIBERTRAC 31 • Foundation Fieldbus

41780-EN-131119

Empty the vessel until the sensor is uncovered.
For this enter the requested pulse rate manually or let the rate be

determined by FIBERTRAC 31. Automatic determination of the pulse

rate should be given preference.
The pulse rate is entered in ct/s. This is the number of counts per

second, i.e. the measured gamma radiation reaching the sensor.
Prerequisites:

Radiation is switched on - Source container is set to "ON"

There is no medium between source container and sensor

You can enter the value for "Adjustment uncovered" (ct/s) manually.

You can have the value for "Adjustment uncovered" determined by

FIBERTRAC 31.

This menu item appears only if you have selected "Single point

adjustment" as adjustment mode (Setup/Adjustment mode).
In this menu item you can adjust at which percentage value of the

max. pulse rate the sensor should switch over.
Since in most cases the radiation is almost completely absorbed

when the sensor is covered, the pulse rate when the sensor is cov-

ered is very low.
The change between the two statuses is sufficiently clear.
Hence a percentage value of 90 % for the Delta I value is recom-

mended.
You select lower values for sensitive detection of material cones or

buildup which cause only partial absorption of the radiation.

This menu item appears only if you have selected under adjustment

mode (setup/adjustment mode) the "Two-point adjustment".
In this menu item you can set the min. pulse rate (ct/s) at which the

sensor should switch over.
Fill the vessel until the FIBERTRAC 31 is covered.

Setup - Delta I (single

point adjustment)

Adjustment "covered"

(two-point adjustment)